Product Description
General
HS-SB116 Manual Call Point, Designed for Fire Alarm Systems and Security Alarm system.
Key Specifications/Special FeaturesAvailable for flush or surface mountingPlastic film on glassTest key inserted from sideOpen circuit with series resistorSuitable for the majority of conventional fire alarm systemsPackaging & Shipping
1 pc/white box;
Packaging Details: as requirementOur Services
OEM & ODM orAny one of our existing product designs can also be modified to meet your specific requirements.FAQ
BEFOREINSTALLING
NOTICE:Thismanualshouldbeleftwiththeowner/userofthisequipment.
GENERALDEscriptION
Theconventionalmanualcallpointdesignedforconventionalfirealarmsystemfor
reportingfireoremergencyconditionbyitsPUSHIN/PULLDOWNhandlelatches.
One470ohmresistorisusedonthePCBboardbetweenZone+andZone-when
theswitchinsideisclosed.Sotheconventionalmanualcallpointisonlyusedwith
conventionalfirealarmcontrolpanel,itisforbiddentobeusedtoothersystem.
OPERATION
Themanualcallpointsprovideatexturedfinger-holdareathatincludesBrailletext.
InadditiontoPUSHINandPULLDOWNtext,therearearrowsindicatinghowto
operatethestation,providedfornon-English-speakingpeople.
Pushinginandthenpullingdownonthehandleactivatesthenormally openalarmswitch.
Oncelatchedinthedownposition,theword“ACTIVATED”appearsatthetopinbrightyellow,
withaportionofthehandleprotrudingatthebottomasavisibleflag.Resettingthestationis
simple:insertthekey,twistonequarter-turn,thenopenthestation’sfrontcover,causingthe
spring-loadedoperationhandletoreturntoitsoriginalposition.Thealarmswitchcanthenbe
resettoitsnormal(non-alarm)positionmanually(byhand)orbyclosingthestation’sfrontcover,
whichautomaticallyresetsthe switch.
LoopDesignandWiring
ThefirealarmcontrolpanelZonewirecanbeconnectedtoterminalloop(+),loop(-) unpolarizedwire.
Ifthemanualcallpointisintheendofthezonewire,a5.6Kresistanceshouldbeconnectedto
terminalloop(+),loop(-).
INSTALLATION
NOTE:Allwiringmustconformtoapplicablelocalcodes,ordinances,andregulations.
MountingIndoorWall
1.Attachmountingbasetowallat1.5meter’shigh.
2.Connectfieldwiringtoterminals
3.Toattachproducttomountingbase.
4.Secureproductbytighteningtheonemountingscrewsinthefrontoftheproducthousing.Why choose us
Advantagewehave
A.experiencedmanufacturers;
B.alibabagoldensupplier,factoryrecognizedbyccc;
C.7/24serviceforyou,allthequestionwillbedealedwithin24hours;
D.Benefityouget
Stablequality---comingfromgoodmaterialandtechnic.
Lowerprice---notcheapestbutthelowestatthesamequality.
Goodservice--satisfactoryservicebeforeandaftersale.
Deliverytime----30daysformassproduction.